Three Phase Smart Energy Meter
                                                                        Three Phase Smart Energy Meter(aMeter300-B)
TECHNICAL SPECIFICATIONS 
Description  Value
   
Voltage  
Reference voltage 3×230V (Direct) 
operating voltage range  70% ~ 130%Un 
   
Current  
Basic current  5A (Direct),10A (Direct) 
Maximum current 60A(Direct),100A (Direct) 
Starting current 0.4%Ib 
   
Accuracy Class 1.0for kWh (Direct)
Class 2.0 for kvarh 
   
Frequency  
Rated frequency (fn) 50Hz
Frequency range ±5%
   
Pulse constant Default:    1600 imp/kWh ,1600 imp/kvarh(Direct)
   
Temperature  
Normal Operation range -25℃ to +55℃
Limit operation range   -40℃ to +70℃
Limit range for storage and transport -40℃ to +85℃ 
   
Humidity Up to 95% non-condensing 
   
Power Consumption  
Power consumption in voltage circuit (active)  ≤2 W
Power consumption in voltage circuit (apparent) ≤10 VA
Power consumption in current circuit ≤1VA 
   
Insulation Strength   
AC voltage test 4kV
Surge Withstand  6kV
Protection class  Class II
   
Electromagnetic Compatibility   
Electrostatic discharges Contact 8kV, air 15kV
Fast transient burst 4kV
Immunity to Impulse voltage (IEC62052-11) 6 kV
Immunity to electromagnetic RF fields 10V/m at reference current, 30V/m without current 
   
Protection degree  IP54 Indoor
   
Breaker Bi-stable relay 
 Lifetime  10000 cycles at ImaxPF=1 and PF=0.5L 
Performance UC2 or UC3 
Maximum switching Voltage 250VAC 
Maximum switching current 120A
Maximum switching power 30kVA
Lifetime ≧ 15 years