Single-Phase Din-Rail Meter

DIN-Rail series are residential split type prepaid electricity meters, with conventional and smart options. They can be configured in Prepaid or Postpaid mode and provide utilities with a high degree of accuracy and reliability, allowing for single-phase connection.

These DIN-Rail meters are designed based on 20-bit Token in accordance with STS specifications, fully complying with DLMS/COSEM IEC standards and certified with DLMS, STS, SABS certificates, and the compact construction design makes it possible to install them in a cluster box with various capacities of 1, 2,5,10, etc. meters. Their robust anti-tampering and prepayment functions make them ideal low-cost devices for revenue collection and protection solutions.

 

 TECHNICAL SPECIFICATION

 

PARAMETERS SM120
Electrical Operating Mode
(Postpaid/Prepaid)
YES
Accuracy (active and reactive energy) 1 for Active (IEC62053-21) and 2 for Reactive
(IEC62053-23)
Connection type 1P2W
Nominal Voltage 110V, 120V, 220V, 230V, 240V ±30%
Nominal Current 5A, IOA
Max Current 80A, IOOA
Starting Current (% 1b) 0.35% 1b
Frequency 50/60Hz ±1%
Power Consumption (V, l) Voltage (IW, 2VA),
Current (1 VA)
RTC ≤O.5s/d (IEC62054-21)
Relay 100A, 250VDC, 100,000 times 
Local Communication Optical Port, RS485
CIU Communication PLC/RF
Uplink Communication PLC/RF
Credit & Alarm LEDs 1 credit LED (Three Colors), 1 Alarm LED
Neutral Line Relay Yes
Environmental Temperature Range
(Operation & Storage)
Operation (-40°C to +70°C) ,
Storage (-40°C to +85°C)
 Relative Humidity ≤95%
Mechanical IP Degree IP54
Meter Case PC+ 10%GF
Terminal 9mm, Brass
Dimension, LWH (mm) 140x90x60
Weight (kg) Approx. 0.5
Functional Energy and/or Currency Credit Charging YES
Load profile 6720 entries, 30 Channels
(Configurable interval: 1 to 60 min)
Billing Periods 12 months 
Event log 550
Measuring Values kW, war, kWh, kVArh, kVA, V, l, F, PF,
Tariffs 6
Anti-Tampering Magnetic Field, Meter cover open/terminal cover open, Bypass, Reverse Energy
Load management Functions Time & Power Thresholds, Over/Under Voltage
Protocols & Standards IEC62056-21/46/47(DLMS), IEC62052-11 , IEC62053-21/23, IEC62055-31 , etc.

 

Download Brochure and Certification